Default Sensor Settings by Product
What this article covers
This article lists the factory default sensor parameter values that fixtures and controllers ship with, organized by product family. Use it as a baseline reference before adjusting settings for your space. For an explanation of what each parameter does and recommended values by space type, see Understanding Sensor Settings.
Overview
Every sensor-equipped device in the Keilton+autani system ships with a set of out-of-the-box default values. These defaults differ by product family—an integrated indoor sensor, a sensor-ready controller, a wet-location sensor, and a line-voltage ceiling sensor each start from a different baseline.
Knowing the defaults helps you:
- Understand how a device behaves before any configuration.
- Identify which parameters you've changed during commissioning.
- Predict device behavior after a factory reset.
Integrated & Sensor-Ready Devices
The table below covers integrated sensor fixtures, sensor-ready controllers, wet-location integrated sensors, and the PPA102S.
| Parameter | Integrated Sensors (IFS108, IFS105, EFS106, EFS104, IFS101) |
Sensor-Ready Controllers (FA102, WPPA102, PPA104S, WF20R) |
Integrated Sensors – Wet Location (EFS106-BH4-W, EFS106-Z10-W, EFS106-AUX-W) |
PPA102S |
|---|---|---|---|---|
| Motion | ON | OFF | ON | OFF |
| Daylight harvesting | ON *¹ | OFF | N/A | N/A |
| T1 | 20 min | 20 min | 20 min | 20 min |
| T2 | 1 min | 1 min | Infinite | 1 min |
| Manual off override | Infinite | Infinite | Infinite | Infinite |
| Dim Level | 50% | 50% | 50% | 50% |
| Sensitivity | 100% | 100% | 100% | 100% |
| Occupancy / Vacancy | Occupancy | Occupancy | Occupancy | Occupancy |
| Linkage | OFF | OFF | OFF | OFF |
| Linkage level | 100% | 100% | 100% | 100% |
| Photocell | N/A | N/A | ON | N/A |
| Photocell ON threshold | N/A | N/A | 5 FC (50 Lux) | N/A |
| Photocell OFF threshold | N/A | N/A | 55 FC (550 Lux) | N/A |
| High trim | 100% | 100% | 100% | 100% |
| Low end trim | 1% or 10% (depends on product) | 1% or 10% (depends on product) | 1% or 10% (depends on product) | 1% or 10% (depends on product) |
| Daylight min dim | = Low end trim | = Low end trim | = Low end trim | = Low end trim |
Footnotes
¹ Daylight harvesting is enabled by default, but the task level is not set by default. Sensors will not begin dimming for daylight harvesting until they are commissioned and configured.
When a photocell is enabled, the sensor ignores the T1/T2 timer settings and responds to ambient light levels instead.
Line-Voltage Ceiling Sensors
These defaults apply to the CS107D and CS107S line-voltage occupancy sensors.
| Parameter | Dual Mode (CS107D.A0) |
Dual Mode (CS107D.B1) |
Single Mode (CS107S) |
|---|---|---|---|
| PIR sensitivity | High | High | High |
| Ultrasonic sensitivity | Middle | Middle | N/A |
| Occupancy / Vacancy | N/A | N/A | Occupancy |
| Triggered by | PIR | PIR or Ultrasonic | N/A |
| Hold on by | Ultrasonic | PIR or Ultrasonic | N/A |
| Hold time | 30 min | N/A | N/A |
| Photocell | ON (100 lux) | N/A | N/A |
| T1 | N/A | 20 min | 20 min |
| T2 | N/A | 1 min | 1 min |
| Manual off override | N/A | Infinite | Infinite |
| Daylight harvesting | N/A | ON *¹ | ON *¹ |
Footnote
¹ Daylight harvesting is enabled by default, but the task level is not set by default. Sensors will not begin dimming for daylight harvesting until they are commissioned and configured.
How to Change These Defaults
Defaults are starting points—you'll typically adjust them during commissioning to suit each space.
- Navigate to the Lights page.
- Long press on a sensor-equipped light to open the Light Dimming page.
- Tap the Sensor Settings icon in the lower right corner.
- Adjust the parameters as needed.
- Tap Save.
For parameter explanations and recommended values by space type, see Understanding Sensor Settings.
Behavior After a Factory Reset
Restoring a device to factory settings returns every parameter above to its default value. On sensor-ready controllers, sensor features (including motion) revert to OFF and must be re-enabled and reconfigured. See Restoring Factory Settings.
Based on Keilton+autani App User Guide v9.8