Skip to content

PPA109S Emergency Lighting & Additional Bridges

Video Tutorial: Watch the companion video V38: PPA109S Emergency Lighting & Additional Bridges for a visual walkthrough.


Overview

The Keilton+autani system includes specialized devices for emergency lighting control, building system integration, and mesh network extension. This article covers the PPA109S Emergency Controller, CR04 Inter-Op Bridge, BG01 485 Bridge, and RP0 Signal Booster.


PPA109S Emergency Lighting Controller

The PPA109S is a UL924-compliant Emergency Lighting Control Device that works with Keilton smart lighting controllers.

Features

Feature Description
Compliance UL924 certified
Function Automatic emergency lighting response
Integration Works with Keilton controllers
Configuration Power fail and restore actions

Adding the PPA109S

  1. Navigate to MoreDevice Info.
  2. Tap Click to Add.
  3. Select the PPA109S when it appears.
  4. Tap Add to confirm.

Configuring the PPA109S

  1. On the Device Info page, long press the PPA109S icon.
  2. The configuration page opens.
  3. Tap the device name to rename (optional).

Power Failure Action

Configure what happens when normal power fails:

Option Description
100% All Lights Default - All lights to full brightness
Scene Activate a specific emergency scene
Group + Level Set specific group to specific level

Power Restore Action

Configure what happens when normal power returns:

Option Description
None Default - No action
Scene Activate a specific scene
Group + Level Set group to level (including Auto)

Repeat Interval

Set a repeat interval to periodically reapply the emergency command. This prevents luminaires from accidentally dimming during emergency situations.


CR04 Inter-Op Bridge

The CR04 connects your Keilton system to external building automation and demand response systems.

Use Cases

  • Building management system integration
  • Demand response program participation
  • Third-party control system connectivity

Adding the CR04

  1. Plug the CR04 into a USB port.
  2. Navigate to MoreDevice Info.
  3. Tap Select to Add.
  4. Select and add the CR04.

Documentation

For detailed setup: - CR04 Inter-Op Bridge User's Guide - Demand Response Instructions

Available at: https://www.litetrace.com/resource


BG01 485 Bridge

The BG01 provides RS-485 communication capability for integration with industrial protocol systems.

Use Cases

  • Building automation controller integration
  • Energy management systems
  • Industrial control equipment

Adding the BG01

  1. Navigate to MoreDevice Info.
  2. Tap Click to Add.
  3. Select the BG01 when it appears.
  4. Add to your zone.

Documentation

Refer to: BG01 485 Bridge Instructions


RP0 Signal Booster

The RP0 extends mesh network coverage in challenging environments where wireless signals may not reach all fixtures reliably.

When to Use

  • Large spaces with distant fixtures
  • Areas with signal-blocking obstacles
  • Installations with weak mesh connectivity
  • Spaces with concrete or metal barriers

Adding the RP0

  1. Plug the RP0 into a USB port.
  2. Navigate to MoreDevice Info.
  3. Tap Select to Add.
  4. Select and add to your zone.

Critical: Zone Association

Important: The RP0 must be added to the zone being commissioned.

When moving to commission a different zone: 1. Delete the RP0 from the current zone 2. Add it to the next zone

The RP0 extends coverage only for the zone it's associated with.

Placement

Position the RP0 strategically between: - The main mesh network (well-connected fixtures) - Distant or poorly-connected fixtures


Adding Devices Summary

All these devices are added via:

  1. More page
  2. Device Info
  3. Click to Add or Select to Add
  4. Select device when it appears
  5. Add to zone

Documentation Resources

Device Documentation
PPA109S PPA109S Instruction Guide
CR04 CR04 Inter-Op Bridge User's Guide, Demand Response Instructions
BG01 BG01 485 Bridge Instructions
RP0 RP0 Commissioning Guide

Resources available at: https://www.litetrace.com/resource


Troubleshooting

Issue Device Solution
Device not appearing All Check USB power/connection
Emergency action not working PPA109S Verify configuration and test
Integration not responding CR04/BG01 Check external system configuration
Coverage still poor RP0 Reposition or add additional boosters
RP0 not helping other zone RP0 Delete and re-add to correct zone

Quick Reference

Device Function Add From
PPA109S Emergency lighting Device Info
CR04 Building automation Device Info
BG01 RS-485 integration Device Info
RP0 Signal extension Device Info


Based on Keilton+autani App User Guide v9.7