Sensor-Ready Controller Setup
Video Tutorial: Watch the companion video V16: Sensor-Ready Controller Setup for a visual walkthrough of these configurations.
Overview
Sensor-ready controllers are fixtures equipped with sensor connectors but shipped with sensor features disabled by default. This article explains how to identify these controllers, enable sensor functionality, and configure them for your installation.
What Are Sensor-Ready Controllers?
Sensor-ready controllers have built-in connectors for external sensors but ship with sensor features turned off. This ensures they work properly out of the box without requiring sensor configuration.
Compatible Models
| Model | Description |
|---|---|
| FA102 | Fixture-mount controller |
| WPPA102 | Wall-pack controller |
| PPA104S | Power pack controller |
| WF20R | Wireless fixture controller |
Configuration Options
You can configure sensor-ready controllers in two ways:
Option 1: With Connected Eco-Sensor
Connect a LiteTrace Eco-Sensor to convert the controller into a full sensor-equipped fixture with local motion detection and daylight harvesting capabilities.
Option 2: Group Linkage Only
Leave the controller without a sensor but enable motion features and group linkage. The fixture responds to sensors in other fixtures within its group.
Enabling Sensor Features (With Eco-Sensor)
If you've connected an Eco-Sensor to the controller:
Step-by-Step Instructions
- Navigate to the Lights page.
- Long press on the sensor-ready controller.
- Tap the Sensor Settings icon.
- Enable Motion sensors toggle.
- Configure sensor parameters:
- T1 (first time delay)
- T2 (second time delay)
- Dim level
- Sensitivity
- If photosensor is connected, enable Daylight harvesting.
- Tap Save.
The controller now responds to the connected Eco-Sensor and operates identically to fixtures with built-in sensors.
Configuring for Group Linkage Only
If no sensor is connected but you want the fixture to respond to other sensors in a group:
Step-by-Step Instructions
- Navigate to the Lights page.
- Long press on the sensor-ready controller.
- Tap the Sensor Settings icon.
- Enable Motion sensors toggle.
- Disable Daylight harvesting (important—no photosensor connected).
- Configure T1, T2, and dim level as desired.
- Tap Save.
- Add the controller to a group with sensor-equipped fixtures (see Groups documentation).
- Enable linkage for that group.
The controller now responds to motion detected by other sensors in its group.
Important Configuration Rules
Daylight Harvesting Without Photosensor
Never enable daylight harvesting on a controller without a photosensor. Without proper sensor input, the fixture dims erratically and unpredictably.
Motion Must Be Enabled for Linkage
Even without a physical sensor attached, you must enable the motion sensors toggle for group linkage to work. The setting enables the firmware to respond to linkage commands from other fixtures.
Factory Reset Behavior
Sensor features disable automatically if you reset the controller to factory settings. After any factory reset, you must re-enable and reconfigure all sensor features.
Default Settings
| Parameter | Default Value |
|---|---|
| Motion | OFF |
| Daylight harvesting | OFF |
| T1 | 20 minutes |
| T2 | 1 minute |
| Dim Level | 50% |
| Sensitivity | 100% |
| Occupancy/Vacancy | Occupancy |
| Linkage | OFF |
Configuration Comparison
| Feature | With Eco-Sensor | Group Linkage Only |
|---|---|---|
| Local motion detection | Yes | No |
| Daylight harvesting | Can enable (if photosensor) | Must disable |
| Independent operation | Yes | No |
| Responds to group sensors | Yes (if in group) | Yes |
| T1/T2 timers | Local control | Follows group |
Connecting Eco-Sensors
Physical Connection
- Power off the fixture.
- Locate the sensor connector on the controller.
- Connect the Eco-Sensor cable.
- Secure the connection.
- Power on the fixture.
After Connection
- Add the fixture to your zone (if not already added).
- Enable sensor features in the app.
- Configure parameters.
- Test sensor operation.
Troubleshooting
| Issue | Cause | Solution |
|---|---|---|
| Erratic dimming | Daylight harvesting enabled without photosensor | Disable daylight harvesting |
| No response to motion | Motion sensors not enabled | Enable motion sensors toggle |
| Linkage not working | Not added to group | Add to group; enable linkage |
| Settings lost | Factory reset performed | Re-enable and reconfigure |
| Sensor not detected | Poor connection | Check physical connection |
Quick Reference
| Configuration | Steps |
|---|---|
| With Eco-Sensor | Connect sensor → Enable motion → Configure parameters → Save |
| Group linkage only | Enable motion → Disable daylight harvesting → Add to group → Enable linkage |
Related Articles
- Understanding Sensor Settings
- Configuring Motion Sensors
- Creating and Managing Groups
- Multiple Group Linkage
Based on Keilton+autani App User Guide v9.7