Skip to content

Sensor-Ready Controller Setup

Video Tutorial: Watch the companion video V16: Sensor-Ready Controller Setup for a visual walkthrough of these configurations.


Overview

Sensor-ready controllers are fixtures equipped with sensor connectors but shipped with sensor features disabled by default. This article explains how to identify these controllers, enable sensor functionality, and configure them for your installation.


What Are Sensor-Ready Controllers?

Sensor-ready controllers have built-in connectors for external sensors but ship with sensor features turned off. This ensures they work properly out of the box without requiring sensor configuration.

Compatible Models

Model Description
FA102 Fixture-mount controller
WPPA102 Wall-pack controller
PPA104S Power pack controller
WF20R Wireless fixture controller

Configuration Options

You can configure sensor-ready controllers in two ways:

Option 1: With Connected Eco-Sensor

Connect a LiteTrace Eco-Sensor to convert the controller into a full sensor-equipped fixture with local motion detection and daylight harvesting capabilities.

Option 2: Group Linkage Only

Leave the controller without a sensor but enable motion features and group linkage. The fixture responds to sensors in other fixtures within its group.


Enabling Sensor Features (With Eco-Sensor)

If you've connected an Eco-Sensor to the controller:

Step-by-Step Instructions

  1. Navigate to the Lights page.
  2. Long press on the sensor-ready controller.
  3. Tap the Sensor Settings icon.
  4. Enable Motion sensors toggle.
  5. Configure sensor parameters:
  6. T1 (first time delay)
  7. T2 (second time delay)
  8. Dim level
  9. Sensitivity
  10. If photosensor is connected, enable Daylight harvesting.
  11. Tap Save.

The controller now responds to the connected Eco-Sensor and operates identically to fixtures with built-in sensors.


Configuring for Group Linkage Only

If no sensor is connected but you want the fixture to respond to other sensors in a group:

Step-by-Step Instructions

  1. Navigate to the Lights page.
  2. Long press on the sensor-ready controller.
  3. Tap the Sensor Settings icon.
  4. Enable Motion sensors toggle.
  5. Disable Daylight harvesting (important—no photosensor connected).
  6. Configure T1, T2, and dim level as desired.
  7. Tap Save.
  8. Add the controller to a group with sensor-equipped fixtures (see Groups documentation).
  9. Enable linkage for that group.

The controller now responds to motion detected by other sensors in its group.


Important Configuration Rules

Daylight Harvesting Without Photosensor

Never enable daylight harvesting on a controller without a photosensor. Without proper sensor input, the fixture dims erratically and unpredictably.

Motion Must Be Enabled for Linkage

Even without a physical sensor attached, you must enable the motion sensors toggle for group linkage to work. The setting enables the firmware to respond to linkage commands from other fixtures.

Factory Reset Behavior

Sensor features disable automatically if you reset the controller to factory settings. After any factory reset, you must re-enable and reconfigure all sensor features.


Default Settings

Parameter Default Value
Motion OFF
Daylight harvesting OFF
T1 20 minutes
T2 1 minute
Dim Level 50%
Sensitivity 100%
Occupancy/Vacancy Occupancy
Linkage OFF

Configuration Comparison

Feature With Eco-Sensor Group Linkage Only
Local motion detection Yes No
Daylight harvesting Can enable (if photosensor) Must disable
Independent operation Yes No
Responds to group sensors Yes (if in group) Yes
T1/T2 timers Local control Follows group

Connecting Eco-Sensors

Physical Connection

  1. Power off the fixture.
  2. Locate the sensor connector on the controller.
  3. Connect the Eco-Sensor cable.
  4. Secure the connection.
  5. Power on the fixture.

After Connection

  1. Add the fixture to your zone (if not already added).
  2. Enable sensor features in the app.
  3. Configure parameters.
  4. Test sensor operation.

Troubleshooting

Issue Cause Solution
Erratic dimming Daylight harvesting enabled without photosensor Disable daylight harvesting
No response to motion Motion sensors not enabled Enable motion sensors toggle
Linkage not working Not added to group Add to group; enable linkage
Settings lost Factory reset performed Re-enable and reconfigure
Sensor not detected Poor connection Check physical connection

Quick Reference

Configuration Steps
With Eco-Sensor Connect sensor → Enable motion → Configure parameters → Save
Group linkage only Enable motion → Disable daylight harvesting → Add to group → Enable linkage


Based on Keilton+autani App User Guide v9.7