CS107D Dual-Technology Sensor Configuration
Video Tutorial: Watch the companion video V34: CS107D Dual-Technology Sensor Configuration for a visual walkthrough.
Overview
The CS107D is a dual-technology ceiling sensor combining PIR (Passive Infrared) and ultrasonic detection. This provides higher accuracy and wider coverage than single-technology sensors, with approximately 600 square feet of room coverage.
Dual-Technology Sensing
PIR (Passive Infrared)
- Detects body heat
- Excellent for detecting people entering a space
- Less prone to false triggers from air movement
- May miss small movements
Ultrasonic
- Emits sound waves and detects motion
- Detects small movements (typing, writing)
- Wider coverage area
- More sensitive to air movement
Combined Benefits
- Reduced false triggers
- Comprehensive coverage
- Configurable trigger/hold logic
A0 vs B1 Series
The CS107D comes in two series with different capabilities:
| Feature | CS107D.A0 | CS107D.B1 |
|---|---|---|
| Voltage | Low voltage | 120-277VAC line voltage |
| Daylight Harvesting | No | Yes (integrated) |
| Timer Control | Simple hold time | T1/T2 timers |
| Dim Level | N/A | Configurable |
| Best For | Basic occupancy | Advanced control with DLH |
Adding a CS107D Sensor
Step-by-Step Instructions
- Navigate to the Switches page.
- Tap the + button.
- Put the sensor into pairing mode.
- Select the sensor when it appears.
- Add to your zone.
Configuring the CS107D
Step-by-Step Instructions
- On the Switches page, tap on the CS107D sensor.
- Tap the Settings button.
- Configure basic settings:
- Name: Enter descriptive name
- Rated Wattage: Set for relay output load
- Group Association: Select light group to control
- Tap Next Step for sensor parameters.
Sensitivity Settings
| Setting | Description |
|---|---|
| PIR Sensitivity | Detection range for heat-based sensing (Low/Med/High) |
| Ultrasonic Sensitivity | Detection range for motion-based sensing (Low/Med/High) |
Trigger and Hold Settings
Configure how motion activates and maintains lights:
| Option | Triggered By | Hold On By | Best For |
|---|---|---|---|
| PIR | PIR only | PIR only | Reducing false triggers from air |
| Ultrasonic | Ultrasonic only | Ultrasonic only | Detecting small movements |
| PIR + Ultrasonic | Both required | Both required | Maximum false trigger reduction |
| PIR or Ultrasonic | Either | Either | Maximum coverage sensitivity |
| None | Manual only | N/A | Vacancy mode operation |
- Tap Save to apply settings.
B1 Series Additional Settings
The CS107D.B1 offers additional configuration:
| Setting | Description |
|---|---|
| T1 | First time delay (full brightness) |
| T2 | Second time delay (warning phase) |
| Dim Level | Brightness during T2 |
| Daylight Harvesting | Automatic dimming based on ambient light |
| Manual OFF Override | Override behavior after manual off |
These settings work similarly to integrated fixture sensors.
Choosing Trigger/Hold Modes
PIR Only
- Use when: Air movement causes false triggers
- Behavior: Only body heat activates/maintains lights
- Trade-off: May miss small seated movements
Ultrasonic Only
- Use when: Detecting small movements is critical
- Behavior: Sound wave detection activates/maintains lights
- Trade-off: More sensitive to HVAC air movement
PIR + Ultrasonic (Both Required)
- Use when: False triggers are a major problem
- Behavior: Both technologies must detect motion
- Trade-off: May be slow to respond
PIR or Ultrasonic (Either Works)
- Use when: Maximum coverage is needed
- Behavior: Either technology activates/maintains lights
- Trade-off: More potential for false triggers
After Configuration
After binding the sensor to a group:
- Navigate to the Groups page.
- Enable Linkage for the associated group.
- If linkage was already enabled, disable and re-enable it.
Troubleshooting
| Issue | Cause | Solution |
|---|---|---|
| False triggers | Ultrasonic too sensitive | Switch to PIR only or reduce sensitivity |
| Missing small movements | PIR only mode | Add ultrasonic to trigger/hold |
| Slow response | Both required mode | Switch to "PIR or Ultrasonic" |
| No response | Sensitivity too low | Increase sensitivity |
Quick Reference
| Action | Steps |
|---|---|
| Add sensor | Switches → + → Pair → Add |
| Configure | Tap sensor → Settings → Configure → Save |
| Set trigger mode | Settings → Next Step → Select trigger/hold options |
| Enable linkage | Groups → Select group → Enable Link |